Beyond Certification: A Multi-Quantitative Post-Occupancy Evaluation of Indoor Environmental Quality in a Platinum-Certified Subtropical University Building

Authors

  • Danyang Du Department of Environmental Science and Engineering, Faculty of Innovation Engineering, Macau University of Science and Technology, Macau, China
  • Xiaoqiang Gong Department of Environmental Science and Engineering, Faculty of Innovation Engineering, Macau University of Science and Technology, Macau, China
  • Kaimin Chen Guangdong Provincial Academy of Building Research Group Co., Ltd., Guangzhou, China
  • Yahong Dong Macao Institute of Green and Net-Zero Technology, Macau University of Science and Technology, Macau, China https://orcid.org/0000-0003-1925-7087

DOI:

https://doi.org/10.15377/2409-9821.2026.13.14

Keywords:

Climate change, Occupant satisfaction, BEAM Plus certification, Subtropical green buildings, Post-occupancy evaluation (POE), Indoor environmental quality (IEQ)

Abstract

Green building certification formally evaluates building performance, while it may not fully capture occupants’ experiences of indoor environmental quality (IEQ) during post-occupancy use. This study presents a post-occupancy evaluation (POE) of a BEAM Plus Platinum-certified academic building at the Macau University of Science and Technology (MUST), using a quantitative evaluation approach that combines a questionnaire survey of occupant satisfaction (n = 108, 90.0% valid response rate) with in-situ physical measurements of key IEQ parameters, including carbon dioxide (CO₂), total volatile organic compounds (TVOC), formaldehyde (HCHO), PM₁₀, thermal conditions, and operational sound level, supplemented by DIALux simulation of artificial-lighting performance. The survey and field measurements were conducted in three classrooms on three days between March 28 and April 11, 2025, during the transition period between classes in a Spring semester. The results indicated that the five IEQ categories received mean scores ranging from 3.65 to 3.94 on a five-point scale, with visual environmental quality being the best while ventilation effectiveness being the worst. In terms of the specific items, natural ventilation adequacy and local overheating/overcooling received the lowest mean scores of 3.47 and 3.14, respectively. Short-term classroom CO₂ concentrations peaked at 897 ppm, and TVOC ranged between 0.001 and 0.008 mg/m³. Thermal measurements showed inter-room variation, with mean temperatures ranging from 23.99 °C to 25.23 °C (a differential of 1.24 °C). Operational sound levels ranged from 46.3 to 57.2 dB(A) in the monitored classrooms. Interpreting occupant feedback with in-situ measurements offers practical, user-centered evidence that bridges the gap between green building certification and actual building performance. The findings provide actionable guidance for follow-up IEQ monitoring and operational optimization in university classrooms.

References

[1] Zhang F, Liu S, Hu W, Yadav M. Effects of indoor environmental quality on human performance and productivity. Frontiers in Built Environment. 2022;8: 1095443. https://doi.org/10.3389/fbuil.2022.1095443

[2] Awada M, Becerik-Gerber B, Hoque S, O'Neill Z, Pedrielli G, Wen J, et al. Ten questions concerning occupant health in buildings during normal operations and extreme events including the COVID-19 pandemic. Building and Environment. 2021;188: 107480. https://doi.org/10.1016/j.buildenv.2020.107480

[3] Al-Khatri H, Alonso González Lezcano R, Toledo L, Moreno-Rangel A. Impact of indoor environmental quality on health and wellbeing in a warming climate. Building Research & Information. 2025;53(1–2): 1–2. https://doi.org/10.1080/09613218.2025.2460001

[4] Ghiai M, Bassaw C, Niknia S. Post-occupancy evaluation and human-centered indoor environmental quality in higher-education buildings: a structured review. Frontiers in Built Environment. 2026;12: 1837203. https://doi.org/10.3389/fbuil.2026.1837203

[5] Brink HW, Loomans MGLC, Mobach MP, Kort HSM. Classrooms' indoor environmental conditions affecting the academic achievement of students and teachers in higher education: a systematic literature review. Indoor Air. 2021;31(2): 405–425. https://doi.org/10.1111/ina.12745

[6] Mustafa FA. Performance assessment of buildings via post-occupancy evaluation: a case study of the building of the architecture and software engineering departments in Salahaddin University-Erbil, Iraq. Frontiers of Architectural Research. 2017;6(3): 412–429. https://doi.org/10.1016/j.foar.2017.06.004

[7] Khoshbakht M, Rasheed E, Baird G. Do green buildings have superior performance over non-certified buildings? Occupants’ perceptions of strengths and weaknesses in office buildings. Buildings. 2022;12(9): 1302. https://doi.org/10.3390/buildings12091302

[8] Mansor AA, Abdullah S, Ahmad AN, Ahmed AN, Zulkifli MFR, Jusoh SM, et al. Indoor air quality and sick building syndrome symptoms in administrative office at public university. Dialogues in Health. 2024;4:100178. https://doi.org/10.1016/j.dialog.2024.100178

[9] Abd Razak A, Saidin H, Buralli R, Cordoba L, Tengku Ibrahim TNB, Nazli SN. Sick building syndrome and indoor air quality in Malaysian bank offices: a cross-sectional analysis. Dialogues in Health. 2025;7: 100249. https://doi.org/10.1016/j.dialog.2025.100249

[10] Mahdizadeh A, Sadat Kia N, Pahlevan D. Prevalence of sick building syndrome and its related factors in medical staff in Iran: a cross-sectional study. Middle East Journal of Rehabilitation and Health Studies. 2024;11(4). https://doi.org/10.5812/mejrh-141003

[11] Dimitroulopoulou S, Dudzinska MR, Gunnarsen L, Hagerhed L, Maula H, Singh R, et al. Indoor air quality guidelines from across the world: an appraisal considering energy saving, health, productivity, and comfort. Environment International. 2023;178: 108127. https://doi.org/10.1016/j.envint.2023.108127

[12] Tang H, Ding Y, Singer BC. Post-occupancy evaluation of indoor environmental quality in ten nonresidential buildings in Chongqing, China. Journal of Building Engineering. 2020;32: 101649. https://doi.org/10.1016/j.jobe.2020.101649

[13] Elsayed M, Pelsmakers S, Pistore L, Castaño-Rosa R, Romagnoni P. Post-occupancy evaluation in residential buildings: a systematic literature review of current practices in the EU. Building and Environment. 2023;236: 110307. https://doi.org/10.1016/j.buildenv.2023.110307

[14] Castaño-Rosa R, Nerweyi D. Bringing post-occupancy evaluation up front to enhance energy efficiency in residential buildings. Building Research & Information. 2025;53(8): 1075–1091. https://doi.org/10.1080/09613218.2025.2538167

[15] Qiu Y, Dong Y. Life cycle assessment of campuses: A systematic review. Energy and Buildings. 2024;319: 114455. https://doi.org/10.1016/j.enbuild.2024.114455

[16] Ye C, Yao L, Meng Y, Zhang Y, He G. Post-occupancy evaluation of green technologies for a high-rise building based on user experience. Sustainability. 2022;14(15): 9538. https://doi.org/10.3390/su14159538

[17] Hou H, Wang Y, Lan H. Student residential apartment performance evaluation using integrated AHP-FCE method. Journal of Building Engineering. 2023;67: 106000. https://doi.org/10.1016/j.jobe.2023.106000

[18] Brink HW, Loomans M, Mobach MP, Kort HSM. A systematic approach to quantify the influence of indoor environmental parameters on students' perceptions, responses, and short-term academic performance. Indoor Air. 2022;32. https://doi.org/10.1111/ina.13116

[19] Li P, Froese TM, Brager G. Post-occupancy evaluation: state-of-the-art analysis and state-of-the-practice review. Building and Environment. 2018;133: 187–202. https://doi.org/10.1016/j.buildenv.2018.02.024

[20] Göçer Ö, Hua Y, Göçer K. Completing the missing link in building design process: enhancing post-occupancy evaluation method for effective feedback for building performance. Building and Environment. 2015;89: 14–27. https://doi.org/10.1016/j.buildenv.2015.02.011

[21] Zaki SA, Damiati SA, Rijal HB, Hagishima A, Abd Razak A. Adaptive thermal comfort in university classrooms in Malaysia and Japan. Building and Environment. 2017;122: 294–306. https://doi.org/10.1016/j.buildenv.2017.06.016

[22] Rizo-Maestre C, Flores-Moreno JM, Nebot Sanz A, Echarri-Iribarren V. Intelligent ventilation and indoor air quality: state of the art review (2017–2025). Buildings. 2026;16(1): 65. https://doi.org/10.3390/buildings16010065

[23] Garman I, Mattsson M, Myhren JA, Persson T. Demand control and constant flow ventilation compared in an exhaust ventilated bedroom in a cold-climate single-family house. Intelligent Buildings International. 2023;15(4): 175–188. https://doi.org/10.1080/17508975.2023.2236993

[24] Moghadam TT, Ochoa Morales CE, Lopez Zambrano MJ, Bruton K, O'Sullivan DTJ. Energy efficient ventilation and indoor air quality in the context of COVID-19: a systematic review. Renewable and Sustainable Energy Reviews. 2023;182: 113356. https://doi.org/10.1016/j.rser.2023.113356

[25] Yunitsyna A, Toska A. Evaluation of the visual comfort and daylight performance of the visual art classrooms. Journal of Daylighting. 2023;10(1): 117–135. https://doi.org/10.15627/jd.2023.9

[26] Mahgoub ME, Alhumaidi A, Osman B, Alshehhi R, Abu Khadir M, AlMahri S. A multi-factor path analysis of visual comfort in classrooms: integrating daylighting, design, and occupant preferences. Architectural Science Review. 2026;69(3): 344–362. https://doi.org/10.1080/00038628.2025.2525292

[27] Yang D, Mak CM. Relationships between indoor environmental quality and environmental factors in university classrooms. Building and Environment. 2020;186: 107331. https://doi.org/10.1016/j.buildenv.2020.107331

[28] Lee MC, Mui KW, Wong LT, Chan WY, Lee EWM, Cheung CT. Student learning performance and indoor environmental quality (IEQ) in air-conditioned university teaching rooms. Building and Environment. 2012;49: 238–244. https://doi.org/10.1016/j.buildenv.2011.10.001

[29] Cheung T, Schiavon S, Graham LT, Tham KW. Occupant satisfaction with the indoor environment in seven commercial buildings in Singapore. Building and Environment. 2021;188: 107443. https://doi.org/10.1016/j.buildenv.2020.107443

[30] Yi L, Xie Y, Lin C. Thermal environment and energy performance of a typical classroom building in a hot-humid region: a case study in Guangzhou, China. Geofluids. 2022;2022: 1–14. https://doi.org/10.1155/2022/3226001

[31] de Wilde P. The gap between predicted and measured energy performance of buildings: a framework for investigation. Automation in Construction. 2014;41: 40–49. https://doi.org/10.1016/j.autcon.2014.02.009

[32] Geng Y, Ji W, Wang Z, Lin B, Zhu Y. A review of operating performance in green buildings: energy use, indoor environmental quality and occupant satisfaction. Energy and Buildings. 2019;183: 500–514. https://doi.org/10.1016/j.enbuild.2018.11.017

[33] Yong NH, Kwong QJ, Ong KS, Mumovic D. Post occupancy evaluation of thermal comfort and indoor air quality of office spaces in a tropical green campus building. Journal of Facilities Management. 2022;20(4): 570–585. https://doi.org/10.1108/JFM-12-2020-0092

[34] Al-Akhzami F, Al-Khatri H, Al-Saadi S, Khan H, Etri T. A comprehensive objective and subjective assessment survey of indoor environmental quality in higher education classrooms in a hot arid climate. Building and Environment. 2024;263: 111870. https://doi.org/10.1016/j.buildenv.2024.111870

[35] Qiu Y, Dong Y. Towards stakeholder-integrated carbon management in higher education institutions: Insights from Macau. Journal of Cleaner Production. 2025;525: 146619. https://doi.org/10.1016/j.jclepro.2025.146619

[36] Lolli F, Marinello S, Coruzzolo AM, Butturi MA. Post-occupancy evaluation's (POE) applications for improving indoor environment quality (IEQ). Toxics. 2022;10(10): 626. https://doi.org/10.3390/toxics10100626

[37] Kim YK, Abdou Y, Abdou A, Altan H. Indoor environmental quality assessment and occupant satisfaction: a post-occupancy evaluation of a UAE university office building. Buildings. 2022;12(7): 986. https://doi.org/10.3390/buildings12070986

[38] Nooraei M, Littlewood JR, Evans NI. Feedback from occupants in ‘as designed’ low-carbon apartments, a case study in Swansea, UK. Energy Procedia. 2013;42: 446–455. https://doi.org/10.1016/j.egypro.2013.11.045

[39] Sanni-Anibire MO, Hassanain MA. Quality assessment of student housing facilities through post-occupancy evaluation. Architectural Engineering and Design Management. 2016;12(5): 367–380. https://doi.org/10.1080/17452007.2016.1176553

[40] Husin HN, Nawawi AH, Ismail F, Khalil N. Correlation analysis of occupants’ satisfaction and safety performance level in low cost housing. Procedia - Social and Behavioral Sciences. 2015;168: 238–248. https://doi.org/10.1016/j.sbspro.2014.10.229

[41] Ministry of Housing and Urban-Rural Development of the People's Republic of China. Assessment standard for green campus: GB/T 51356-2019. Beijing: China Architecture & Building Press; 2019. (in Chinese)

[42] Iowa State University. Iowa Environmental Mesonet (IEM): ASOS/AWOS/METAR Data Archive [Internet]. Ames (IA): Iowa State University; [cited 2026 Oct 10]. Available from: https://mesonet.agron.iastate.edu/request/download.phtml

[43] Environmental Protection Bureau, Macau SAR Government. Macau guidelines for indoor air quality in general public places. Macau: Environmental Protection Bureau; 2014. (in Chinese)

[44] Macau Special Administrative Region. Chief Executive Dispatch No. 96/2020: Acoustic Standard. Official Gazette of the Macau Special Administrative Region. 2020 Apr 14;Series I(15): 3520–3523. (in Chinese)

[45] Education and Youth Development Bureau, Macau SAR Government. Guidelines for the licensing of private educational institutions (continuing education). Macau: Education and Youth Development Bureau; 2024. (in Chinese)

[46] Raynham P. The SLL code for lighting. London: Chartered Institution of Building Services Engineers; 2012.

[47] BEAM Society Limited. BEAM Plus Existing Buildings (Global Version): Version 1.0. Hong Kong: BEAM Society Limited; 2024.

[48] Pastore L, Andersen M. Building energy certification versus user satisfaction with the indoor environment: findings from a multi-site post-occupancy evaluation (POE) in Switzerland. Building and Environment. 2019;150: 60–74. https://doi.org/10.1016/j.buildenv.2019.01.001

[49] Merema B, Delwati M, Sourbron M, Breesch H. Demand controlled ventilation (DCV) in school and office buildings: lessons learnt from case studies. Energy and Buildings. 2018;172: 349–360. https://doi.org/10.1016/j.enbuild.2018.04.065

[50] Haddad S, Synnefa A, Ángel Padilla Marcos M, Paolini R, Delrue S, Prasad D, et al. On the potential of demand-controlled ventilation system to enhance indoor air quality and thermal condition in Australian school classrooms. Energy and Buildings. 2021;238: 110838. https://doi.org/10.1016/j.enbuild.2021.110838

[51] Papadopoulos S, Kontokosta CE, Vlachokostas A, Azar E. Rethinking HVAC temperature setpoints in commercial buildings: the potential for zero-cost energy savings and comfort improvement in different climates. Building and Environment. 2019;155: 350–359. https://doi.org/10.1016/j.buildenv.2019.03.062

[52] Hosamo H, Mazzetto S. Data-driven ventilation and energy optimization in smart office buildings: insights from a high-resolution occupancy and indoor climate dataset. Sustainability. 2025;17(1): 58. https://doi.org/10.3390/su17010058

[53] Oh J, Wong W, Castro-Lacouture D, Lee J, Koo C. Indoor environmental quality improvement in green building: occupant perception and behavioral impact. Journal of Building Engineering. 2023;69: 106314. https://doi.org/10.1016/j.jobe.2023.106314

[54] Roberts CJ, Edwards DJ, Hosseini MR, Mateo-Garcia M, Owusu-Manu D-G. Post-occupancy evaluation: a review of literature. Engineering, Construction and Architectural Management. 2019;26(9): 2084–2106. https://doi.org/10.1108/ecam-09-2018-0390

[55] Al Mughairi M, Beach T, Rezgui Y. Post-occupancy evaluation for enhancing building performance and automation deployment. Journal of Building Engineering. 2023;77: 107388. https://doi.org/10.1016/j.jobe.2023.107388

Downloads

Published

2026-11-14

Issue

Section

Articles

Categories

How to Cite

1.
Beyond Certification: A Multi-Quantitative Post-Occupancy Evaluation of Indoor Environmental Quality in a Platinum-Certified Subtropical University Building. Int. J. Archit. Eng. Technol. [Internet]. 2026 Nov. 14 [cited 2026 Nov. 14];13(3):284-311. Available from: https://www.avantipublishers.com/index.php/ijaet/article/view/1857

Similar Articles

1-10 of 82

You may also start an advanced similarity search for this article.